
A modern laundry room needs two dedicated circuits: a 20-amp, 120-volt circuit for the washer (NEMA 5-20R) and a 30-amp, 240-volt 4-wire circuit for an electric dryer (NEMA 14-30R). The 4-prong dryer receptacle has been the NEC requirement for new installations since 1996; older 3-prong NEMA 10-30R outlets are grandfathered but should be upgraded during any laundry work. In Northern Virginia, AJ Long Electric installs or upgrades these circuits for $400–$900 each, permit and inspection included.
NEC 210.11(C)(2) requires a dedicated 20-amp branch circuit for the laundry receptacle (washer). NEC 250.140 requires 4-wire (hot-hot-neutral-ground) terminations for electric dryers — the old 3-wire setup is grandfathered in existing installations but cannot be installed new.
20A 120V for washer. 30A 240V for electric dryer. Gas dryers use a standard 120V outlet but the gas line itself requires a licensed plumber.
Standard NEMA 5-20R for washer. NEMA 14-30R for electric dryer (4-prong, code-required since 1996). If you have an old NEMA 10-30R 3-prong dryer outlet, that's grandfathered but upgrading to 14-30R is recommended during any laundry work.
Typical 2026 pricing
$400 – $900 per circuit
Adding both washer (20A) and dryer (30A) dedicated circuits as a paired job typically runs $700–$1,200 since the runs and terminations can be done together. Replacing an existing 3-prong NEMA 10-30R with a code-compliant 4-prong NEMA 14-30R requires running a new 4-wire cable from the panel — typically $500–$800. Permit and inspection included.
Laundry appliances are two of the highest-draw loads in a typical home, and they were never meant to share a circuit. A washer's motor and an electric dryer's heating element can each pull most of a circuit's capacity on their own — run them at the same time on a shared circuit and you get nuisance breaker trips at best, and overheated conductors at worst. That is exactly why the National Electrical Code carves out dedicated circuits for the laundry area: NEC 210.11(C)(2) requires at least one dedicated 20-amp branch circuit serving the laundry receptacle, and that circuit is not allowed to feed lighting or outlets in other rooms.
The electric dryer is in a different category altogether. It runs on 240 volts, drawing power across both legs of your panel through a dedicated 30-amp double-pole breaker. There is no sharing a 240-volt dryer circuit — it exists solely to feed the dryer. When AJ Long Electric quotes a laundry room, we look at both loads together: the 120-volt washer circuit and the 240-volt dryer circuit are usually run in the same trip, which is why pairing them is more cost-effective than adding one now and the other later.
In older Northern Virginia homes — and there are a lot of them in Fairfax, Arlington, Alexandria, and the inner Loudoun and Prince William suburbs — it is common to find a single circuit feeding both the washer and a 120-volt utility outlet, or a 3-prong dryer receptacle that predates the modern 4-wire requirement. Bringing those installations up to current code is one of the most frequent laundry calls we get, especially when a homeowner buys a new appliance that ships with a 4-prong cord.
If your dryer receptacle has three slots, it is an old NEMA 10-30R — the pre-1996 standard. That configuration carried two hot legs and a single conductor that served as both neutral and ground. The problem is that bonding neutral and ground together at the appliance means the dryer's metal cabinet can become energized if the neutral ever opens. The 1996 NEC closed that gap by requiring 4-wire terminations for electric dryers under what is now NEC 250.140: two hots, a separate neutral, and a separate equipment ground, landing on a NEMA 14-30R receptacle.
Existing 3-prong installations are grandfathered, so you are not legally required to rip one out just because it is old. But you cannot install a new 3-prong outlet, and the safe, code-compliant fix when you are upgrading anyway is to run a fresh 4-wire 10/3 cable from the panel and swap in a 14-30R receptacle. We never recommend the 3-to-4-prong plug adapters sold online: any adapter that re-bonds neutral and ground reintroduces the exact hazard the 4-wire rule was written to eliminate.
A correct upgrade typically runs $500–$800 because it involves a new home run from your panel, not just a receptacle swap. If your laundry is finished and the panel is far away, fishing the cable adds time; if the panel backs onto the laundry wall or the run is accessible through a basement or attic, it goes quickly. Either way, the work is permitted, inspected, and warrantied.
Homeowners often ask why a 30-amp circuit is standard when their dryer's manual lists a smaller running load. The answer is in the code's load-calculation rules. Under NEC 220.54, a household electric clothes dryer is calculated at 5,000 watts — or the appliance nameplate rating if it is higher — regardless of the lower average draw during a typical cycle. At 240 volts, that demand lands squarely in 30-amp territory, which is why the 10-gauge copper conductor and 30-amp double-pole breaker are the long-standing standard pairing for residential dryers.
The washer side is more modest: a 20-amp, 120-volt dedicated circuit on 12-gauge copper covers the washer motor and any laundry-area outlet on that circuit. Because laundry rooms put receptacles near plumbing, NEC 210.8(A) requires GFCI protection there, so we install the washer circuit on a GFCI device as part of any modern installation. On the panel itself, current code also calls for AFCI protection on these branch circuits, which we handle with combination AFCI/GFCI breakers where appropriate.
Getting the sizing and protection right is not just a box to check for the inspector — it is what keeps a laundry room from becoming a recurring source of tripped breakers, warm receptacles, and shortened appliance life. When we hand off a job, both circuits are correctly sized, correctly protected, labeled in the panel, and signed off by the local jurisdiction.
| Spec | Washer circuit | Electric dryer circuit |
|---|---|---|
| Voltage | 120V | 240V |
| Breaker | 20A single-pole | 30A double-pole |
| Wire (copper) | 12/2 with ground | 10/3 with ground |
| Receptacle | NEMA 5-20R | NEMA 14-30R (4-prong) |
| Required protection | GFCI (NEC 210.8(A)) | 4-wire termination (NEC 250.140) |
| Governing NEC article | 210.11(C)(2) | 220.54 / 250.140 |
| Typical installed cost | $400–$700 | $500–$900 |
We confirm the existing panel capacity, identify whether the existing dryer outlet is 3-wire or 4-wire, and quote the work — separating washer and dryer if they're on the same circuit.
Local jurisdiction permit (Fairfax County, Arlington, Alexandria, Loudoun, Prince William, etc.). Filed under our master electrician license.
Home-run a 10/3 (4-wire) cable from the panel to the dryer location for the new 30A circuit. Home-run a 12/2 cable for the dedicated 20A washer circuit. Fished through walls/ceilings where possible.
NEMA 14-30R for electric dryer (4-prong). Standard NEMA 5-20R for washer. AFCI breakers in the panel per current code; GFCI on the washer circuit (it's near plumbing).
Local jurisdiction inspector verifies the 4-wire dryer termination, GFCI on the washer, and panel work. We schedule and meet on-site.
3-prong (NEMA 10-30R) is the old standard from before 1996. It carries two hot legs and a combined neutral/ground — which is unsafe because the dryer's metal chassis is bonded to neutral. 4-prong (NEMA 14-30R) is the current code: separate neutral and ground, isolating the dryer chassis from the neutral path. New dryers come with 4-prong cords; old 3-prong outlets are grandfathered in existing installations.
No. Plug adapters that re-bond neutral and ground are technically code violations and unsafe. The proper fix is to run a 4-wire cable from the panel and install a new NEMA 14-30R receptacle. Cost is usually $500–$800.
Yes per current code (NEC 210.8(A) — laundry areas). Older homes with the original washer circuit may not have GFCI; we add it as part of the upgrade. GFCI is critical near plumbing because of the water-electricity proximity.
Same wiring requirements — you need both a 20A washer circuit and a 30A 4-wire electric dryer circuit (or 120V for the dryer half of a heat-pump or vented stackable). The stackable mounting saves floor space but not electrical capacity.
Yes, and we recommend it during any laundry remodel. Adding the 30A 4-wire circuit when the wall is open costs little incremental; doing it later (after the gas dryer is in place) costs significantly more. Future-proofing for electrification (gas-to-electric transition) is common practice in Northern Virginia builds.
A 30-amp 240V dryer circuit is wired with 10-gauge copper — specifically a 10/3 cable carrying two hots, a neutral, and a ground — landed on a 30-amp double-pole breaker. The dedicated 20-amp washer circuit uses 12-gauge copper (12/2 with ground) on a 20-amp single-pole breaker. Per NEC 220.54, a household electric dryer is calculated at 5,000 watts or its nameplate rating, whichever is larger, which is why 30 amps is the standard size even though many dryers draw less in normal operation.
Most laundry-circuit jobs are completed in a single visit of two to four hours, depending on how far the laundry room is from the panel and whether walls are open. Replacing a 3-prong dryer outlet with a 4-prong on an existing run is faster; pulling brand-new circuits from the panel to a relocated laundry area, or fishing cable through finished walls, takes longer. Permit filing and the jurisdiction inspection are scheduled separately and do not extend the on-site work.
We cite the published standards this dedicated-circuit work is held to. Verify any of them yourself.